AUD405.00 DRF-PR-115VAC-0/10VDC-4/20
Description
The DRF series DIN rail signal conditioners are designed to accept a broad range of input signals, such as ac and dc voltage and current, frequency, temperature (thermocouple and RTD), and process transducers, and provide standard process outputs of either 4 to 20 mA, or 0 to 10 Vdc. The DRF series feature a modern housing design, that is easily mounted on standard 35 mm DIN rails. Connections are safely and securely made through pluggable screw terminal connectors, with input and output connections on the opposite sides of the module.Range Code | Range |
0/5MA | 0 to 5 mA |
0/50MA | 0 to 50 mA |
0/20MA | 0 to 20 mA |
4/20MA | 4 to 20 mA |
0/1VDC | 0 to 1 Vdc |
0/10VDC | 0 to 10 Vdc |
SPECIFICATIONS Accuracy: <0.2% full scale Linearity: <<0.1% full scale Thermal Drift: 150 ppm/°C typical (max <200ppm/°C) Response Time: <70 mS (90% of signal)at 20 Hz -3 dB Impedance and Overvoltage:
Power: 24 Vdc ±10%, 230 Vac ±10% 50/60 Hz, 115 Vac ±10% 50/60 Hz Power Consumption: <3.8 VA |
Output: 4 to 20 mA and 0 to 10 Vdc Maximum Voltage Output: 11 Vdc approx. Minimum Voltage Output: -1 Vdc approx. Minimum Load Resistance (Voltage): >1 KΩ Maximum Current Output: 22 mA approx. Maximum Current Output: -1.5 mA approx. Maximum Load Resistance (current): >400 Ω Vexc Output for Transducers:+15 Vdc ±10% (22 mA max.) Electrical Connections: Plug-in screw terminals Protection: IP-30 MECHANICAL DIMENSIONS Weight: (DC Powered Models): 120 g (4.2 oz) (AC Powered Models): 200 g (7 oz) Dimensions: (DC Powered models): 110 H x 22.5 W x 93 mm D (4.3 x 0.9 x 3.7") (AC Powered models): 110 H x 37 W x 93 mm D (4.3 x 1.46 x 3.7") Operating Temperature: 0 to 60°C (32 to 140°F) Storage Temperature: -20 to 70°C (-4 to 158°F) |
Part Number Builder