Application
• Fast < 20 ms response time for measuring signals produced
by torque, position, current & acceleration sensors.
• User configurable bipolar or unipolar I/O means the DRST-DC is
suitable for nearly any DC voltage or current conversion.
• Freely programmable between ±300 VDC and ±100 mA.
The excitation source allows measurement of a 2-wire or 3-wire transmitter, or a potentiometer.
• Converts narrow bipolar inputs to wide bipolar or unipolar
outputs, e.g., ± 1 volt input = ± 10 volt or 4 to 20 mA output.
• Configurable input limits control the output value for increased
safety.
• ±20 VDC buffered voltage output for controlling devices like
the PVG 32 valve (6 to 18 VDC).
Technical Characteristics
• The latest analog and digital techniques are used to obtain maximum accuracy and immunity to interference.
• Possibility of output safety read back by selecting 4 to 20 mA
output.
• The current output can drive up to 1000 Ω, with an
adjustable response time of 0.0…60.0 seconds.
• Exceptional mA output load stability of < 0.001% of span/100
Ω.
• Meets the NAMUR NE21 recommendations, ensuring high accuracy in harsh EMC environments.
• Meets the NAMUR NE43 recommendations, allowing the control system to easily detect a sensor error.
• Each unit is tested to a high 2.3 kVAC, 3-port galvanic
isolation level.
• Excellent signal to noise ratio of > 60 dB. Mounting/Installation/Programming
• Very low power consumption means units can be mounted
side by side without an air gap – even at 60°C (140ºF) ambient temperature.
• Configuration, monitoring, 2-point process calibration and more are accomplished using either the DRSL-Display detachable display or the DRST-CM detachable digital communication enabler.
• All programming can be password-protected.
Specifications Environmental Conditions Operating Temperature: -20 to 60°C Storage Temperature: -20 to 85°C Calibration Temperature: 20 to 28°C Relative Humidity: < 95% RH (non-cond.) Protection degree: IP20 Mechanical Specifications Dimensions (H x W x D): 109 x 23.5 x 104 mm Dimensions (H x W x D) with 4501/4511: 109 x 23.5 x 116/131 mm Weight Approx: 250 g Weight Incl. 4501/4511 (approx.): 285 g/350 g
DIN Rail Type: DIN EN 60715/35 mm Wire Size: 0.13 to 2.08 mm2 AWG 26 to 14 stranded wire Screw Terminal Torque: 0.5 Nm Common Specifications
Supply Supply Voltage, Universal: 21.6 to 253 VAC, 50 to 60 Hz or 19.2 to 300 VDC Max. Required Power: = 2.5 W Internal Power Dissipation: = 2.0 W Isolation Voltage Test Voltage: 2.3 kVAC Working Voltage: 250 VAC (reinforced)/500n VAC (basic) Response Time: Response Time: (0 to 90%, 100 to 10%) < 20 ms Auxiliary Supplies 2-wire Loop Supply: > 16 V @ 20 mA 3-wire Loop Supply: > 18 to < 28 V @ 23 to 0 mA Loop Supply Limitation: 27 to 35 mA avg., < 80 mA peak Reference Voltage: 2.5 VDC ±0.5% Reference Voltage, Load: 0 to 15 mA Current Limit, Reference Voltage: < 60 mA Programming: Communication enabler 4511/Programming front 4501 Signal Dynamics, Input: 24 bit Signal Dynamics, Output: 18 bit Signal/Noise Ratio: > 60 dB Bandwidth: > 40 Hz Accuracy: Better than 0.05% of selected range EMC Immunity Iinfluence: < ±0.5% of span Extended EMC Immunity: NAMUR NE21, A Criterion, Burst: < ±1% of span
Conducted Emission, class A: 150 kHz to 10 MHz Input Specifications Current Input
Signal Range: ±100 mA Programmable Measurement Ranges: 0 to 1, 0 to 5, 1 to 5, 0 to 20, 4 to 20,
±1, ±5, ±10, ±20, ±50, ±100 mA
Custom Configurable Signal Range: ±100 mA Min. Measurement Range (span): 0.5 mA Input Voltage Drop: 0.6 V @ 20 mA nom. Voltage Input
Signal range: ±300 VDC Programmable Measurement Ranges: 0 to 0.1, 0 to 1, 0.2 to 1, 0 to 2.5, 0 to 5,
1 to 5, 0 to 10, 2 to 10, 0 to 100, 0 to 300, ±0.1, ±1, ±2.5, ±5, ±10, ±100, ±300 V Custom Configurable Signal Range:±300 V Min. Measurement Range (span): 25 mV Input Resistance: Nom. 3 MΩ (> 2.5 VDC) Input Resistance:Nom. > 10 MΩ (= 2.5 VDC) Potentiometer Input 3-wire Potentiometer Input: 0 to 100% Reference Voltage: 2.5 V Calibration Resistance: 5 kΩ Min. Potentiometer Resistance: 200 Ω Output Specifications
Current Output Signal Range: 0 to 23 mA (unipolar) Signal Range: -23 to 23 mA (bipolar) Custom Config. Output Range: ±20 mA Min. Signal Range: 4 mA Load (@ Current Output): = 1000 Ω/± 20 V @ ±20 mA Current Limit: = 28 mA (unipolar) Current Limit: ± 28 mA (bipolar) Load Stability: = 0.001% of span / 100 Ω Response Time, Programmable: 0.0 to 60.0 s Passive 2-wire mA Output
Programmable Ranges: 0 to 20 and 4 to 20 mA Ext. 2-Wire Loop Supply Range: 3.5 to 28.8 VDC
Voltage Output
Programmable Signal Ranges: 0/0.2 to 1; 0/1 to 5 ; 0/2 to 10 V Programmable Signal Ranges: ±1, ±5 and ±10 V Programmable Signal Ranges:Direct or Inverted action Load (@ Voltage Output): = 500 kΩ Response Time, Programmable: 0.0 to 60.0 s Shunted Voltage Output Signal Range: ± 1.2 V/± 12 V Programmable Standard Ranges: 0 to 1, 0 to 2.5, 0 to 5, 1 to 5, 0 to 10, 2 to 10 V ±1, ±2.5, ±5, ±10 V Min. Span: 0.8 V Custom Config. Output Range: ±10 V Load, Min: > 500 kΩ
Buffered Voltage Output
Signal range: ± 23 V Programmable Standard Ranges: 0 to 1, 0.2 to 1, 0 to 2.5, 0 to 5,1 to 5, 0 to 10, 2 to 10, 0 to 20, 4 to 20; ±1, ±2.5, ±5, ±10, ±20 V Min. Span: 0.8 V Custom Config. Output Range: ±20 V Current Limit: < 50 mA Load, Min: > 2 kΩ Observed Authority Requirements
LVD: 2014/35/EU EMC: 2014/30/EU RoHS: 2011/65/EU Approvals
UL: UL 508/CC22.2 no. 14
† All amounts shown in AUD
We noticed you are from the US. Visit your local site for regional offers and live support.