AUD67.95 SSRL240DC25
Description
The Omega's SSRL series of solid state relays are used to control large resistance heaters in conjunction with temperature controllers. Solid state relays are SPST, normally open switching devices with no moving parts, capable of millions of cycles of operation. By applying a control signal, an SSR switches ON the ac load current, just as the moving contacts do on a mechanical contactor. Three-phase loads can be controlled using 2 or 3 SSR’s. Use 3 SSR’s for Y or star 3-phase loads using a neutral line. Two SSR’s will control “delta” loads with no neutral line. Three solid state relays are also used when there is no neutral load to provide redundancy and extra assurance of control.Specifications | 10 Amp | 25 Amp | 50 Amp | 75 Amp | 100 Amp |
Max On State Current | 10 A | 25 A | 50 A | 75 A | 100 A |
Max On State Current | 100 mA | ||||
Max 1-Cycle Surge | 150 A | 300 A | 750 A | 1000 A | 1200 A |
Max 1 sec Surge | 30 A | 75 A | 150 A | 225 A | 300 A |
12T (60 Hz), A2sec | 416 | 937 | 2458 | 5000 | 6000 |
Input-Control Signal | Output | |||||
Model No. | Type | Control Signal Voltage | Control Signal Turn-On | Control Signal Turn-Off | Max Input Current | Peak Voltage* (60 Sec. Max.) |
SSRL240AC10 SSRL240AC25 SSRL240AC50 SSRL240AC75 SSRL240AC100 | ac Control Signal | 90 to 280 Vac | 90 Vac | 10 Vac | 10 mA | 800 V |
SSRL240DC10 SSRL240DC25 SSRL240DC50 SSRL240DC75 SSRL240DC100 | dc Control Signal | 3 to 32 Vdc | 3 Vdc | 1 Vdc | 14 mA | 800 V |
SSRL660AC50 SSRL660AC75 SSRL660AC100 | ac Control Signal | 90 to 280 Vac | 90 Vac | 10 Vac | 10 mA | 1200 V |
SSRL660DC50 SSRL660DC75 SSRL660DC100 | dc Control Signal | 4 to 32 Vdc | 4 Vdc | 1 Vdc | 14 mA | 1200 V |
Model No. | Nominal ac Line Voltage | Nominal Load Current | Max. Contact Voltage Drop | Max. Off-State Leakage (25°C max. ambient) | ||
120 Vac | 240 Vac | 440 Vac | ||||
SSRL240AC10 SSRL240AC25 SSRL240AC50 SSRL240AC75 SSRL240AC100 | 24 to 280 Vac | 10 A 25 A 50 A 75 A 100 A | 1.6 V | 0.1 mA | 0.1 mA | N/A |
SSRL240DC10 SSRL240DC25 SSRL240DC50 SSRL240DC75 SSRL240DC100 | 24 to 280 Vac | 10 A 25 A 50 A 75 A 100 A | 1.6 V | 0.1 mA | 0.1 mA | N/A |
SSRL660AC50 SSRL660AC75 SSRL660AC100 | 48 to 660 Vac | 50 A 75 A 100A | 1.6 V | 0.25 mA | 0.25 mA | 0.25 mA |
SSRL660DC50 SSRL660DC75 SSRL660DC100 | 48 to 660 Vac | 50 A 75 A 100 A | 1.6 V | 0.25 mA | 0.25 mA | 0.25 mA |
Part Number Builder