Cart  |  Contact  |  Help  |  auinfo@dwyeromega.com  | 
Toll-Free in Australia: 1800 106 210
International+65 6415 5353

Thermistor Temperature Transmitter

TX206TH

Thermistors Temperature Transmitters | TX206TH

Thermistors Temperature Transmitters

AUD153.77 TX206TH

CE
  • Supports Many Thermistor Types
  • 2-Wire, Loop Powered
  • 4 to 20 mA Output
  • PC Configurable Ranges (Requires Programmer)
  • High Stability
  • Free Configuration Software Download
Process Measurement and Control Instruments - View related products

Description

The TX206TH is a cost effective “smart” in head transmitter that accepts thermistor temperature sensors and converts sensor output over a configured range to a standard industrial (4 to 20) mA transmission signal.

A variety of thermistor types are available when using the configuration software: select thermistor type, temperature range, units and burnout direction, without requiring calibration equipment.

PC configuration is performed quickly using our new USB port driven configurator by simply connecting two clips to the TX206TH loop terminals and following the software instructions. Calibration set-up may be saved as a file on the PC for later use.

Alternatively, a single pushbutton and LED indicator allows the user to configure transmitter range against a manually set input condition. A red LED is included to help guide the user. The LED also operates as a sensor error indicator.

Transmitters can be factory configured for any range specified at the time of order, removing the need for user configuration. Extra lead time is required.

Specifications at 20°C (68°F)
INPUT
Sensor Type: Thermistor
Sensor Connection: Screw terminal
Minimum Span: 5°C (9°F)
Accuracy (Typical): ±0.2°C, ±0.2% of reading
Thermal Drift: ±0.02%/°C
OUTPUT
Output Type: 2-wire (4 to 20) mA current loop
Output Range: 4.0 to 20.0 mA
Output Connection: Screw terminal
Maximum Output: 21.5 mA
Minimum Output: <3.75 mA
Accuracy: mA output /2000 or 5 uA (whichever is greater)
Loop Voltage Effect: 0.2 uA/V
Thermal Drift: ±2 uA/°C
Maximum Output Load: [(Vsupply-10)/21]KΩ; example: 666Ω @ 24V)
Thermistor Types: Please refer to configuration software for complete up to date list: 3KB (44005, 44030), 5KB (44007, 44034), 10KB (44016,44036) 10KH (44006, 44031), 30KH (44008), 2252KB (44004, 44033)
General Specifications
Response Time: 1 second
Start-Up Time: 2 seconds (I out <4 mA during start up)
Warm-Up Time: 1 minute to full accuracy
Power Supply: 10 to 30 Vdc
ENVIRONMENTAL
Ambient Operating Range: -40 to 85°C (-40 to 185°F)
Ambient Storage Temperature: -50 to 90°C (-58 to 194°F)
Ambient Humidity Range: 10 to 90% RH non condensing
PHYSICAL
Dimensions: 21 H x 43 mm Dia (0.83 x 1.7")
Weight: 31 g (1 oz) (encapsulated)
Place Order(Specify Model Number)
Part Number/ Desc.
Qty
Description
TX206TH
AUD153.77
Availability: 6 weeks
 
Thermistor temperature transmitter
TX206TH-UKFS
Consult Sales  
Availability: 
 
 
Thermistor temperature transmitter, factory scaled
USB-CONFIG-TH
AUD195.14
Availability: 4 weeks
 
USB interface cable (required for user scaling)
All amounts shown in AUD
Note: Comes complete with operator’s manual.
Note: To order with factory scaling use model number TX206TH-UKFS and advise thermistor type, range and output scaling required.
Ordering Example: (1) TX206TH Thermistor temperature transmitter, AUD153.77  plus (1) USB-CONFIG-TH ISB interface cable, AUD195.14, AUD153.77 + 195.14 = AUD348.91